IPGSM-4G

IPGSM-4GC
Commercial fire alarm communicator, with a built-in dialer, offering contact ID reporting with any Fire Alarm Control Panel

The IPGSM-4GC is a commercial fire alarm communicator that offers contact ID reporting with any Fire Alarm Control Panel (FACP) that has a built-in dialer. This single or dual path communicator connects directly to the primary and secondary communication ports of a fire panel's Digital Alarm Communicator Transmitter (DACT). It offers three selectable reporting paths which include: Cellular only, IP only, or IP primary/cellular backup.

Features & Benefits:

  • Saves the cost of two dedicated phone lines
  • Selectable reporting paths and supervision intervals to meet NFPA, Chapter 26 requirements
  • Built-in power supply module
  • Works over any type of customer provided Ethernet 10/100 based network connection (LAN or WAN), DSL modem or cable modem

Specifications

Electrical Specifications:

  • Transformer: – Primary 120VAC, 60Hz, 0.5A
  • Secondary: 18VDC, 50VA
  • Battery:
    • One 12 V 7.0 AH lead-acid battery (not supplied)
    • Battery charging current: 1 Amp maximum
    • Battery discharge current: Standby 230mA, Active 950mA

Cabinet Specifications:

  • Dimensions: 14.875" H x 12.75" W x 3.0" D (37.8 cm H x 32.4 cm W x 7.6 cm D)
  • Color: Red

Listings:

  • ULC Listed: S789
  • CSFM: 7300-1645:0199
  • FDNY: COA #6150

Resources

Basket Size :
0 MB out of 50 MB

Document Name Asset Type Type & Size Modified Date
Brochures pdf | 2.68 MB 04/24/2019
Data Sheets pdf | 0.05 MB 06/26/2017
Engineering Specs doc | 0.13 MB 05/02/2017